RV and camper power check
Pick your shore-power hookup and the appliances you want running at once. You get the running watts, the worst start-up (usually the rooftop AC), whether each leg stays inside the 80% limit, and, if you choose a station with maker-verified specs, whether it can run the lot and for how long.
Pre-filled
30 A: AC, fridge, converter · 50 A: two ACs and kitchen · RV AC on a power station
How this is worked out
- Hookup: 30 A at 120 V is 3,600 W on one leg. 50 A is 120/240 V: two 120 V legs of 6,000 W each. Continuous loads are planned at 80% of the breaker (NEC 210.20(A), 2023 NEC): 2,880 W on a 30 A leg, 4,800 W per leg on 50 A. Loads are balanced across the two legs, largest first.
- Running watts are summed as if everything runs at once (the safe side). Average watts apply the typical duty cycle (an AC compressor runs about half the time) and give the daily energy and the runtime.
- Worst start-up = the running total with the hungriest load swapped for its start-up draw, plus a 10% margin. The soft-start figure uses the same planning assumption as the soft-start check (peak cut 60%, never below 1.5 × running). It is an assumption, not a promise; read the kit's spec page.
- Runtime = rated Wh × 85% ÷ average watts. A station's own spec (continuous, surge, 240 V) comes from the maker's page, checked on the date in our catalogue.
- All appliance figures are typical planning values, not measurements of your RV. Read your own labels. To run your AC from a solar-charged station see solar panels to recharge; for a bigger source see generator size; for feeding a house see inlet and cord matcher.
Related: RV AC on a power station · window AC · backup power calculator. We list no prices and have not hands-on tested any product.