Generator extension cord size
Enter what you plug into the cord, the voltage and how long the cord is. You get the smallest cord gauge that is rated for the current and keeps voltage drop within 3%, with the working shown.
Pre-filled
1,800 W at 120 V, 50 ft · 3,000 W at 120 V, 100 ft · 30 A at 240 V, 25 ft
How this is worked out
- Current = watts ÷ volts, taking power factor as 1 (the safe side). A load that runs for hours is sized at 125%.
- Ampacity comes from 2023 NEC Table 400.5(A)(1), copper flexible cord, Column A (the lower column, used for every cord here). The cord must be rated at or above the design current.
- Voltage drop = 2 × amps × ohms per 1000 ft × length ÷ 1000, with resistance from Chapter 9 Table 8. 3% is a recommendation (210.19(A) Informational Note 4), not a code requirement. Motors and compressors need extra: see voltage drop and soft-start.
- The cord is only as good as its plugs and the generator outlet. Check the outlet rating on the generator itself. To power a house, do not use a cord into a wall outlet: see the inlet and cord matcher and inlet breaker size. For fumes and placement see generator safety.