What can a 30 amp generator hookup run?

A 30 A generator inlet (usually an L14-30 on 240 V, sometimes a TT-30 on 120 V) is the common size for portable generators. The cable and breaker set the ceiling; the generator's own rating may be lower.

The ceiling, from amps times volts

CircuitMaximum (A × V)Continuous (80%)
30 A at 120 V (one leg)3,600 W2,880 W
30 A at 240 V (both legs)7,200 W5,760 W

Continuous loads are kept to 80% of the breaker rating (NEC 210.19(A) and 215.2(A) for loads over 3 hours). The generator itself must also be rated for the watts you draw. A 240 V circuit feeds two 120 V legs that must be balanced when you split loads between them.

Typical appliances against that ceiling

ApplianceTypical runningTypical start-upOn 30 A, 120 V onlyOn 30 A, 240 V
Refrigerator (full size)150 W1,200 Wyesyes
Chest freezer100 W800 Wyesyes
Microwave (1,000 W cooking)1,500 W1,500 Wyesyes
Coffee maker1,000 W1,000 Wyesyes
Electric kettle1,500 W1,500 Wyesyes
Electric range or oven3,000 W3,000 Wneeds 240 Vyes
Gas furnace blower fan500 W1,500 Wyesyes
Window AC (8,000 BTU)700 W2,000 Wyesyes
Central AC (3 ton)3,500 W9,000 Wneeds 240 Vruns, but start-up too high
Electric space heater1,500 W1,500 Wyesyes
Box or ceiling fan60 W60 Wyesyes
Electric blanket100 W100 Wyesyes
Sump pump (1/3 HP)800 W2,400 Wyesyes
Well pump (1/2 HP)1,000 W3,000 Wneeds 240 Vyes
CPAP (humidifier off)40 W40 Wyesyes
CPAP with heated humidifier90 W90 Wyesyes
Oxygen concentrator300 W600 Wyesyes
Wi-Fi router and modem20 W20 Wyesyes
Satellite internet dish75 W75 Wyesyes
Laptop60 W60 Wyesyes
Desktop PC and monitor250 W250 Wyesyes
TV (55 inch LED)100 W100 Wyesyes
Phone charging (4 phones)20 W20 Wyesyes
LED lights (5 bulbs)45 W45 Wyesyes
Garage door opener500 W1,000 Wyesyes
Aquarium pump and heater50 W50 Wyesyes
Washing machine500 W1,500 Wyesyes

All appliance numbers are typical values from our own table, not measurements of your device; the label wins. "Yes" means both the running and start-up figure fit under the maximum, and the running figure fits under the continuous limit.

Step-start: add the loads one at a time

Motors (fridge, sump pump, furnace fan, AC) draw several times their running watts for a second or two when they start. Start the biggest one first, then add the rest, and keep the total running load under the continuous limit. Example on a 30 A, 120 V circuit: fridge, sump pump, furnace fan, LED lights and router run together at 1,515 W. If the sump pump starts while the others run, the peak is about 3,115 W (running total plus the largest extra start-up draw). Limit: 3,600 W peak, 2,880 W continuous. That fits.

240 V versus 120 V

Well pumps, central AC and ranges are 240 V loads and need a 240 V inlet and a matching generator outlet. Many 120 V appliances can be moved between the two legs of the panel, so the usable total on 240 V is about twice the 120 V figure only when the loads split evenly.

Safety

Never feed a panel through a dryer outlet or a "suicide cord". A generator inlet must be wired with an interlock or transfer switch, and the work needs a licensed electrician and a permit where required. Local amendments apply. Run generators outdoors, well away from windows.